<p>Bench-scale fire testing has gained popularity as a highly controllable and cost-effective solution, overcoming many of the shortcomings of traditional large-scale fire resistance tests. Whereas gas-fired radiant panels have demonstrated significant success in this area, the present study introduces a novel High-Intensity Fast-Response Electric radiant Panel (HIFREP). Utilizing electrically operated radiation emitters, it provides more precise and quasi-instantaneous control over the thermal boundary conditions. HIFREP delivers high and stable heat fluxes up to 105&#xa0;kW/m<sup>2</sup>, and, due to the low thermal inertia of the emitters, can rapidly adjust its output to changes in the input. In this regard, the time constant of the emitters has been found to be less than 1&#xa0;s, both during heating and cooling. It eliminates gas combustion and hence avoids the need for extraction hoods when testing the fire performance of non-combustible materials, making it suitable for traditional structural testing laboratories. The presented High-Intensity Fast-Response Electric radiant Panel also provides a reliable tool for the validation of FEM simulation results by accurately replicating the thermal boundary conditions in structural fire engineering analyses.</p>

错误:搜索内容不能为空,请输入英文关键词
错误:关键词超出字数限制,请精简
高级检索

High-Intensity Fast-Response Electric Radiant Panel (HIFREP) to Impose Fire Equivalent Heat Fluxes on Building Elements with Enhanced Thermal Boundary Conditions Accuracy

  • Florian Put,
  • Balša Jovanović,
  • Evelien Symoens,
  • Andrea Lucherini,
  • Bart Merci,
  • Ruben Van Coile

摘要

Bench-scale fire testing has gained popularity as a highly controllable and cost-effective solution, overcoming many of the shortcomings of traditional large-scale fire resistance tests. Whereas gas-fired radiant panels have demonstrated significant success in this area, the present study introduces a novel High-Intensity Fast-Response Electric radiant Panel (HIFREP). Utilizing electrically operated radiation emitters, it provides more precise and quasi-instantaneous control over the thermal boundary conditions. HIFREP delivers high and stable heat fluxes up to 105 kW/m2, and, due to the low thermal inertia of the emitters, can rapidly adjust its output to changes in the input. In this regard, the time constant of the emitters has been found to be less than 1 s, both during heating and cooling. It eliminates gas combustion and hence avoids the need for extraction hoods when testing the fire performance of non-combustible materials, making it suitable for traditional structural testing laboratories. The presented High-Intensity Fast-Response Electric radiant Panel also provides a reliable tool for the validation of FEM simulation results by accurately replicating the thermal boundary conditions in structural fire engineering analyses.