<p>This study aims to experimentally investigate the combustion products of fires suppressed/extinguished by two water-based fire suppression systems, namely, sprinklers and water mist systems. A total of thirteen experiments were conducted with various suppression system configurations, i.e., with a sprinkler, a low-pressure (LP) water mist, and a high-pressure (HP) water mist, at operating pressures ranging from 2 to 60 bar and water flow rate ranging from 10 to 206 L/min. Each experiment was conducted twice, except for the baseline experiment with no suppression. The fuel was a high-density polyethylene (HDPE) pallet placed on two wood pallets. During all the stages of fire development, suppression with water, and post-suppression, the combustion products were sampled through Fourier-Transform Infrared Spectroscopy (FTIR) using a gas analyzer capable of operating in high humidity. The main combustion products identified were CO<sub>2</sub>, CO, and H<sub>2</sub>O. In addition, NO<sub>x</sub> (nitrogen oxides), C<sub>x</sub>H<sub>y</sub> (light-weight hydrocarbons)<sub>,</sub> and HCN were present in relatively high concentrations. All the tested fire suppression systems were effective in reducing the fire size and cooling down the gases. However, when the fire could not be immediately extinguished, the NO<sub>x</sub>, C<sub>x</sub>H<sub>y</sub>, and HCN concentrations were higher than those in the baseline experiment. Moreover, it is observed that the HP water mist system was more effective than the sprinkler and low-pressure water mist systems in reducing the amount of combustion gases during suppression, resulting in lower Fractional Effective Doses (FED). It was observed that the combustion products returned to ambient conditions after five minutes of deactivation. The results from this study provide much-needed validation data for the effectiveness of water-based suppression systems, not only in reducing the fire size but also in reducing the production of acute toxic gases, which is important for considerations regarding evacuation, firefighting, and post-extinguishment conditions.</p>

错误:搜索内容不能为空,请输入英文关键词
错误:关键词超出字数限制,请精简
高级检索

The Impact of Water-Based Fire Suppression Systems on Combustion Products

  • Lei Jiang,
  • Davood Zeinali,
  • Kemal Sarp Arsava,
  • Dag Olav Snersrud

摘要

This study aims to experimentally investigate the combustion products of fires suppressed/extinguished by two water-based fire suppression systems, namely, sprinklers and water mist systems. A total of thirteen experiments were conducted with various suppression system configurations, i.e., with a sprinkler, a low-pressure (LP) water mist, and a high-pressure (HP) water mist, at operating pressures ranging from 2 to 60 bar and water flow rate ranging from 10 to 206 L/min. Each experiment was conducted twice, except for the baseline experiment with no suppression. The fuel was a high-density polyethylene (HDPE) pallet placed on two wood pallets. During all the stages of fire development, suppression with water, and post-suppression, the combustion products were sampled through Fourier-Transform Infrared Spectroscopy (FTIR) using a gas analyzer capable of operating in high humidity. The main combustion products identified were CO2, CO, and H2O. In addition, NOx (nitrogen oxides), CxHy (light-weight hydrocarbons), and HCN were present in relatively high concentrations. All the tested fire suppression systems were effective in reducing the fire size and cooling down the gases. However, when the fire could not be immediately extinguished, the NOx, CxHy, and HCN concentrations were higher than those in the baseline experiment. Moreover, it is observed that the HP water mist system was more effective than the sprinkler and low-pressure water mist systems in reducing the amount of combustion gases during suppression, resulting in lower Fractional Effective Doses (FED). It was observed that the combustion products returned to ambient conditions after five minutes of deactivation. The results from this study provide much-needed validation data for the effectiveness of water-based suppression systems, not only in reducing the fire size but also in reducing the production of acute toxic gases, which is important for considerations regarding evacuation, firefighting, and post-extinguishment conditions.