<p>This short paper comments on a recent article published in <i>Electrical Engineering</i> (Springer), where a vertical needle-shaped conductor is analyzed, first alone and then added to a horizontal star grounding electrode. The authors claim that the addition of the needle reduces the grounding impedance of the system; we tend to believe that the conclusion may be correct; unfortunately, the published results may not be reliable, as the mathematical/physical description of the electromagnetic field presented is, in our opinion, incomplete, mainly because the time-varying magnetic field within the ground has been ignored.</p>

错误:搜索内容不能为空,请输入英文关键词
错误:关键词超出字数限制,请精简
高级检索

Comments on the design of needle-shaped tower grounding devices

  • J. A. Brandão Faria

摘要

This short paper comments on a recent article published in Electrical Engineering (Springer), where a vertical needle-shaped conductor is analyzed, first alone and then added to a horizontal star grounding electrode. The authors claim that the addition of the needle reduces the grounding impedance of the system; we tend to believe that the conclusion may be correct; unfortunately, the published results may not be reliable, as the mathematical/physical description of the electromagnetic field presented is, in our opinion, incomplete, mainly because the time-varying magnetic field within the ground has been ignored.